This page contains affiliate links. If you purchase through them we may earn a small commission at no extra cost to you. Learn more
Solar Panel Wiring Diagram: How a UK System Connects

Understanding how a solar panel system connects from roof to meter helps you have better conversations with installers, spot potential problems, and follow what's happening during installation. This guide walks through each component in the electrical path of a typical UK grid-tied solar-plus-battery system.
Educational Overview Only
This article is an educational walkthrough of system architecture — not installation instructions. All electrical connections in a solar PV system must be made by a qualified electrician or an MCS-registered installer. The DC side of a solar system is always live whenever panels are exposed to light. There is no isolator that makes panels themselves safe to touch.
The Full Wiring Path: Step by Step
A grid-tied solar-plus-battery system follows a defined electrical path from the panels on the roof to the grid connection at the meter. Here is that path in order.
1. Solar Panels on the Roof
Solar panels generate electricity as DC (direct current) — a constant flow of electrons in one direction. Each panel produces a voltage (typically 30–50V open circuit) and a current that depends on sunlight intensity.
Panels are wired together in strings — a series chain where the voltage of each panel adds up. A string of 6 panels might produce 250V DC under load. Multiple strings are sometimes wired in parallel to increase current capacity.
The cable used for this DC wiring is H1Z2Z2-K (commonly called "PV cable" or "solar cable") — typically 4mm² cross-section. This cable is specifically designed for outdoor DC use: UV-resistant, double-insulated, and rated for the high voltages that strings produce. Standard twin-and-earth (T+E) mains cable must never be used for DC PV wiring.
Connections between panels use MC4 connectors — weatherproof click-lock connectors designed for solar use. They are gender-specific: a male MC4 connects only to a female MC4, reducing the risk of wiring errors.
2. DC Isolator (Roof Level)
Before the DC cable run leaves the roof, a DC isolator is mounted close to the panels. This is a switch rated for DC voltage that allows the string to be disconnected for maintenance — for example, if an installer needs to work on the wiring between the panels and the inverter.
This isolator is required under BS 7671 Section 712 (the UK wiring regulations for solar PV systems). It must be:
- Rated for DC use (AC isolators are not suitable for DC circuits)
- Labelled clearly as a PV array isolator
- Accessible but protected from tampering
Importantly, this isolator does not make the panels themselves safe — the panels are still generating voltage whenever there is light. Only covering the panels with an opaque material reduces their output.
3. DC Cable Run from Roof to Inverter
The H1Z2Z2-K PV cable runs from the roof-level isolator to the inverter location — typically a garage, utility room, or wall near the consumer unit. This cable run:
- Must use H1Z2Z2-K throughout — not swapped to T+E partway
- Must be clipped or contained appropriately (cable tray, conduit, or properly fixed runs)
- Must be separated from other cable types where possible, or clearly identified
- If buried underground (for ground-mounted systems), must be buried at the correct depth per BS 7671 Regulation 522.8.10 — 450mm under garden soil, 600mm under driveways or paths — inside armoured cable (SWA) or UV-stable conduit
The DC voltage in this cable can reach 450–600V DC on larger systems — considerably higher than the 230V AC mains. This is why correct cable selection and containment matters.
4. DC Isolator (Inverter Level)
A second DC isolator is positioned immediately before the inverter at floor level. This allows the installer (or electrician) to safely isolate the inverter from the DC side without going to the roof. It serves as the main working isolator for inverter maintenance.
Some inverters incorporate this isolator internally. Where that is the case, the installer's documentation should confirm this satisfies the BS 7671 Section 712 requirement.
5. Hybrid Inverter
The hybrid inverter is the central component of a modern solar-plus-battery system. It performs several functions simultaneously:
- DC to AC conversion: Converts the DC from the panels into 230V 50Hz AC for your home
- Battery management: Charges and discharges the battery bank based on generation, consumption, and any time-of-use schedule you set
- Grid synchronisation: Matches the AC output exactly to the grid frequency (50Hz) so the two can work together
- Export management: Controls how much electricity flows back to the grid
The inverter communicates with a CT clamp (current transformer) — a sensor clamped onto the meter tails (the thick cables between your meter and consumer unit). The CT clamp tells the inverter in real time how much electricity the home is importing or exporting. This information lets the inverter decide whether to direct solar into the home, into the battery, or out to the grid.
Popular hybrid inverters in the UK include the GivEnergy Gen 3, Solis RHI, SunSynk, Fox ESS H series, and Sungrow SH series.
6. Generation Meter
A generation meter is a separate meter that measures the total AC output from the inverter — all the electricity the system has produced, regardless of whether it was used in the home or exported.
Generation meters were mandatory under the old Feed-In Tariff (FiT) scheme, which closed to new applicants in 2019. Under the current Smart Export Guarantee (SEG), a SMETS2 smart meter handles export measurement directly, so a dedicated generation meter is optional for new installs. However, some homeowners retain one for monitoring purposes or to calculate self-consumption ratios.
7. Consumer Unit (Fuse Board)
The AC output from the inverter connects to your consumer unit (often called a fuse board or distribution board) via a dedicated MCB (miniature circuit breaker). This MCB protects the inverter AC circuit in the same way a ring main circuit is protected.
The consumer unit must meet current regulations:
- Non-combustible metal enclosure — required since BS 7671 Amendment 3 (2015). Plastic consumer units must have been upgraded if solar is being added.
- SPD (Surge Protection Device) — required from Amendment 4 (2022) in most new or significantly modified consumer unit installations. An SPD protects against voltage spikes from lightning or grid events.
The connection point in the consumer unit is sometimes called the load side connection — the inverter feeds into the same busbars that supply the rest of the circuits. This means solar generation is used by whatever loads are running in the home first, reducing import from the grid.
8. Smart Meter (SMETS2)
A SMETS2 smart meter (the current generation of UK smart meters) measures both import and export in half-hourly intervals. It communicates this data to your energy supplier automatically.
This is the key meter for:
- Billing: Your supplier charges you only for net import
- SEG payments: Export is measured at the smart meter; your SEG supplier pays you based on this data
- Time-of-use tariffs: Agile, Flux, Go, and other tariffs depend on half-hourly data from the smart meter
If you do not have a SMETS2 meter, your supplier should install one free of charge. Some older SMETS1 meters are fully functional in this role, but SMETS1 meters fitted by a previous supplier may have lost their smart functionality — worth checking.
9. Grid Connection
Beyond the meter, the wiring belongs to your Distribution Network Operator (DNO) — the company that owns and operates the local electricity network. You do not own or control anything past the meter.
Your installer is responsible for notifying the DNO before the system is commissioned. For systems up to 3.68 kW single-phase, this is a G98 notification (submitted by the installer, typically within 28 days of installation). For larger systems, a G99 application with DNO approval is required before installation begins.
Battery Wiring Variants: DC-Coupled vs AC-Coupled
Where the battery sits in the system determines the coupling type — and this affects both efficiency and complexity.
DC-Coupled Battery
In a DC-coupled system, the battery connects directly to the inverter's DC bus — the internal DC circuitry of a hybrid inverter. Solar DC and battery DC share the same bus inside the inverter. The inverter performs a single DC-to-AC conversion for everything that flows to the home.
Efficiency: DC coupling involves fewer conversion steps. A typical hybrid inverter running solar through the battery to the home achieves ~95–98% round-trip efficiency. Very little energy is wasted.
Wiring: The battery bank connects via DC cables (typically 35–70mm² for the short run between battery and inverter) and a dedicated DC isolator. The battery management system (BMS) communicates with the inverter via a data cable (often CAN bus or RS485).
Limitation: The battery must be compatible with the hybrid inverter. You cannot mix and match freely — check the inverter's approved battery list.
AC-Coupled Battery
In an AC-coupled system, the battery has its own separate inverter/charger (called a battery inverter). This connects on the AC side — to the consumer unit or a dedicated AC circuit — rather than to the hybrid inverter's DC bus.
Efficiency: AC coupling requires additional conversion steps:
- Solar DC → AC (solar inverter): ~97%
- AC → battery DC (battery inverter): ~95%
- Battery DC → AC (battery inverter again, on discharge): ~95%
The result is a round-trip efficiency of approximately 90–94% — lower than DC coupling. On a 10 kWh battery cycling daily, this means roughly 100–200 Wh/day more lost to heat.
Advantage: AC coupling works with any existing inverter — including string inverters and microinverter systems. If you already have solar without battery storage, adding an AC-coupled battery (such as a Tesla Powerwall) avoids replacing your existing inverter.
| DC-Coupled | AC-Coupled | |
|---|---|---|
| Round-trip efficiency | ~95–98% | ~90–94% |
| Works with existing string inverter | No | Yes |
| Works with microinverters | No | Yes |
| Battery choice | Inverter-dependent | Wider range |
| Best for | New installs | Retrofits |
For a detailed comparison, see AC-Coupled vs DC-Coupled Battery Systems.
What to Ask Your Installer
When getting quotes, you can use this wiring walkthrough as a checklist:
- Where will the roof-level DC isolator be located?
- What cable type and size will be used for the DC run?
- Where will the inverter be sited, and is that location suitable (ventilation, ambient temperature)?
- How will the CT clamp be fitted, and where?
- Will the consumer unit need upgrading to a metal enclosure or SPD fitted?
- Is the existing smart meter SMETS2, and is it set up for export measurement?
- Will the G98/G99 notification be submitted by the installer?
A good installer will be able to answer all of these clearly and walk you through the proposed layout before work begins.
Ask for a System Diagram
Many installers will produce a simplified wiring diagram specific to your installation as part of the commissioning documentation. Ask for this — it is useful for future maintenance, fault diagnosis, and for any electrician or installer who works on the system later.
Share this article
Stay informed
Get free solar updates direct to your inbox
Related reading

MC4 Connectors Explained: Types, Crimping, and Compatibility
MC4 solar connectors explained for UK DIYers. Types, crimping guide, compatibility warnings, and where to buy genuine connectors.

Solar PV Cable UK: Types, Sizes, and Where to Buy
H1Z2Z2-K solar cable explained. Sizing guide for 2.5, 4, and 6mm DC cable, voltage drop, and cheapest UK suppliers.

Running Solar Cable to Your Garden: Trench Depth, Armoured Cable, and Regs
UK rules for burying solar cable outdoors. BS 7671 trench depths, armoured cable vs conduit, and surface-mount alternatives.
Switch to Octopus Energy
Get 50 credit when you switch. We get 50 too — win-win.
What does this mean for YOUR home?
Design your perfect solar setup in under 3 minutes. Free, no sign-up required.
Build Your Solar System